4-2-4: NFPA 70 NATIONAL ELECTRICAL CODE ADOPTED; EXCEPTIONS; ADDITIONS:
   (A)   Adopted: The National Fire Protection Association National Electric Code, 2014 edition (NFPA 70-2014) is hereby adopted by reference as the Electrical Code of the Village subject to such deletions and additions of sections as are hereinafter provided.
   (B)   Exceptions: In lieu of Article 334, Nonmetallic Sheathed Cable: types NM, NMC and NMS all lighting and receptacle circuits must be enclosed in electrical metallic tubing, except for flexible metallic drops not to exceed four feet (4') in length.
   (C)   Wiring System: All wiring system shall be installed in EMT, IMC or rigid conduit.
   (D)   Promulgation Of Rules: The President and Board of Trustees may adopt rules and regulations to implement the provisions of this chapter as may be recommended by the Building Officer of the Village acting as Electrical Commission or the chief electrical inspector. (Ord. 18-09, 8-27-2018, eff. 1-1-2019)