922.11 GREASE INTERCEPTOR REQUIREMENTS.
(a) All Food Service Establishments shall provide wastewater acceptable to the City under the requirements and standards established herein before discharging to any public sewer. Any Food Service Establishment required to provide FOG pretreatment shall install, operate, and maintain an adequately sized grease interceptor necessary to maintain compliance with the objectives of this Chapter.
(b) Grease interceptor sizing shall conform to the specifications of the current edition of the Ohio Plumbing Code, as enforced by the City of Aurora Planning, Zoning and Building Division. Minimum outside grease interceptor size shall be 1,000 gallons. GI installation shall conform to the current edition of the International Plumbing Code, Ohio version.
(c) The grease interceptor shall be installed at a location where it shall be at all times easily accessible for inspection, cleaning, and removal of accumulated grease.
(Ord. 2010-184. Passed 2-14-11.)