(A) Section 101.1 of the 2018 International Fuel Gas Code is amended to read, in its entirety, as follows:
101.1 Title. These regulations shall be known as the Apache Junction Fuel Gas Code, hereinafter referred to as “this code.”
(B) Sections 101.3 through 110.4 inclusive are deleted in their entirety. See Vol. I, Chapter 7, Article 7-1, Division of Building Safety and Inspection Administrative Code.
(C) Delete the last sentence of Section 406.4 and add the following:
Tests required by this code that are performed utilizing dial gauges shall be limited to gauges having the following pressure graduations or incrementations:
Required pressure tests of ten (10) pounds (69kPa) or less shall be performed with gauges of one-tenth (1/10) pound (0.7 kPa) incrementation or less.
Required pressure tests exceeding ten (10) pounds (69kPa) but less than one hundred (100) pounds (689 kPa) shall be performed with gauges of one (1) pound (6.9 kPa) incrementation or less.
Required pressure tests exceeding one hundred (100) pounds (689 kPa) shall be performed with gauges incremented for two percent (2%) or less of the required test pressure.
Test gauges shall have a pressure range not greater than twice the test pressure applied.
(Ord. 1475, passed 6-19-2019)