The deletions from and modifications and amendments to the 2011 National Electrical Code are as follows:
Article 200 Wiring and Protection
210.52 (G) Basements, Garages and Accessory Buildings add the following:
210.52 (G) (3). A minimum of one ceiling receptacle outlet shall be installed at each overhead garage door in all attached garages and detached garages.
210.70 (1) Habitable Rooms add the following:
210.70 (1) Habitable Rooms Exception No. 3: Switches in bathrooms shall be at least 5 feet from the inside edge of any bathtub or shower unless protected by ground-fault circuit interrupter protection for personnel. All light and/or exhaust fixtures located above bathtubs or showers shall be protected by ground-fault circuit interrupter protection for personnel and approved for this type of location.
210.70 (2) (a) Additional Locations delete and replace with the following:
210.70(2) (a) At least one wall switch-controlled lighting outlet shall be installed in hallways, stairways, attached garages and detached garages. Said wall switch shall not be located beyond five feet (5') from the point of entry to a room, including cellars or basements.
Article 334 Nonmetallic-Sheathed Cable: Types NM, NMC & NMS delete in its entirety.
Article 338 Service-Entrance Cable: Types SE & USE delete in its entirety.
Article 354 Nonmetallic Underground Conduit with Conductors: Type NUCC delete in its entirety.
Article 362 Electrical Nonmetallic Tubing: Type ENT delete in its entirety.
Article 378 Nonmetallic Wire Ways delete in its entirety.
Article 382 Nonmetallic Extensions delete in its entirety.
Article 388 Surface Nonmetallic Raceways delete in its entirety.
Article 394 Concealed Knob-And-Tube Wiring delete in its entirety.
Article 396 Messenger Supported Wiring delete in its entirety.
Article 398 Open Wiring on Insulators delete in its entirety.
(Ord. O-18-025, 7-19-2018)