§ 150.170  AMENDMENTS TO THE INTERNATIONAL PROPERTY AND MAINTENANCE CODE.
IPMC Section 101.1 Title
To read:
   These regulations shall be known as the Property Maintenance Code of Will County hereinafter referred to as "this code."
IPMC Section 102.3 Application of other codes
(A)   Delete any reference to the International Plumbing Code
(B)   Delete any reference to the International Zoning Code
(C)   Insert: "To read Illinois Plumbing Code and Will County Zoning Ordinance."
(D)   Delete the last sentence in its entirety.
IPMC Section 103.5 Fees
Add after the last sentence:
   See Will County Land Use Adopted Fee Schedule.
IPMC Section 201.3 Terms Defined in Other Codes
(A)   Delete International Zoning Code
(B)   Delete International Plumbing Code
(C)   Insert: "To read Illinois Plumbing Code and Will County Zoning Ordinance."
IPMC Section 304.14 Insect Screens
   Insert the dates "from March 15 to November 1"
IPMC Section 502.5 Public Toilet Facilities
   Delete International Plumbing Code and insert Illinois Plumbing Code
IPMC Section 505.1 General
   In the last sentence delete "In accordance with the International Plumbing Code" and insert: "To read Illinois Plumbing Code."
IPMC Section 602.2 Residential Occupancies
To read:
   Dwellings shall be provided with heating facilities capable of maintaining a room temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms based on the winter outdoor design temperature of 6,155 heating degree days. Cooking appliances shall not be used to provide space heating to meet the requirements of this section.
IPMC Section 602.3 Heat Supply
Delete first sentence in its entirety and insert the following.
To read:
   Every owner and operator of any building who rents, leases or lets one or more dwelling units, rooming units, dormitory or guest rooms on terms, either expressed or implied, shall furnish heat to the occupants and maintain a temperature of not less than 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms from October 1 to April 30th
IMPC Section 602.3 Heat Supply
Exception:
   Delete the last sentence in its entirety:
IPMC Section 602.4 Occupiable Work Spaces
To read:
   Indoor occupiable work spaces shall be supplied with heat during "habitable working hours" of not less than 65°F (18°C).
(Ord. 14-103, passed 5-15-2014; Am. Ord. 18-115, passed 5-17-2018; Am. Ord. 18-116, passed 5-17-2018)