(a) Prohibited Discharge Standards.
(1) General Prohibitions. No user shall introduce or cause to be introduced into the POTW any pollutant or wastewater which causes pass through or interference. These general prohibitions apply to all users of the POTW whether or not they are subject to categorical pretreatment standards or any other National, State, or local pretreatment standards or requirements.
(2) Specific Prohibitions. No user shall introduce or cause to be introduced into the POTW the following pollutants, substances, or wastewater:
A. Pollutants which create a fire or explosive hazard in the POTW, including, but not limited to, wastestreams with a closed-cup flashpoint of less than 140°F (60°C) using the test methods specified in 40 CFR 261.21;
B. Wastewater having a pH less than 5.0 or otherwise causing corrosive structural damage to the POTW or equipment;
C. Solid or viscous substances in amounts, which will cause obstruction of the flow in the POTW resulting in interference.
D. Pollutants, including oxygen-demanding pollutants (BOD, etc.), released in a discharge at a flow rate and/or pollutant concentration which, either singly or by interaction with other pollutants, will cause interference with the POTW;
E. Wastewater with a temperature which will inhibit biological activity in the treatment plant resulting in interference, but in no case wastewater which causes the temperature at the introduction into the treatment plant to exceed 104°F (40°C);
F. Petroleum oil, non-biodegradable cutting oil, or products of mineral oil origin, in amounts that will cause interference or pass through;
G. Pollutants which result in the presence of toxic gases, vapors, or fumes within the POTW in a quantity that may cause acute worker health and safety problems;
H. Trucked or hauled pollutants, except at discharge points designated by MACM in accordance with Section 931.03.
I. Noxious or malodorous liquids, gases, solids, or other wastewater which, either singly or by interaction with other wastes, are sufficient to create a public nuisance or a hazard to life, or to prevent entry into the sewers for maintenance or repair;
J. Wastewater which imparts color which cannot be removed by the treatment process, such as, but not limited to, dye wastes and vegetable tanning solutions, which consequently imparts color to the treatment plant's effluent, thereby violating MACM NPDES permit;
K. Wastewater containing any radioactive waste or isotopes except in compliance with applicable State or Federal regulations;
L. Storm water, surface water, ground water, artesian well water, roof runoff, subsurface drainage, swimming pool drainage, condensate, deionized water, non-contact cooling water, and unpolluted wastewater, unless specifically authorized by MACM.
M. Sludges, screening, or other residues from the pretreatment of industrial wastes;
N. Medical wastes, except as specifically authorized by MACM in a wastewater discharge permit;
O. Wastewater causing, alone or in conjunction with other sources, the treatment plant's effluent to fail a toxicity test;
P. Detergents, surface-active agents, or other substances which may cause excessive foaming in the POTW;
Q. Wastewater causing two readings on an explosion hazard meter at the point of discharge into the POTW, or at any point in the POTW, of more than five percent (5%) or any single reading over ten percent (10%) of the Lower Explosive Limit of the meter.
Pollutants, substances, or wastewater prohibited by this Section shall not be processed or stored in such a manner that they could be discharged to the POTW.
(b) National Categorical Pretreatment Standards. The categorical pretreatment standards found at 40 CFR Chapter I, Subchapter N, Parts 405-471 are hereby incorporated.
(1) Where a categorical pretreatment standard is expressed only in terms of either the mass or the concentration of a pollutant in wastewater, MACM may impose equivalent concentration of mass limits in accordance with 40 CFR 403.6 (c).
(2) When wastewater subject to a categorical pretreatment standard is mixed with wastewater not regulated by the same standard, MACM shall impose an alternate limit using the combined wastestream formula in 40 CFR 403.6 (e).
(3) A user may obtain a variance from a categorical pretreatment standard if the user can prove, pursuant to the procedural and substantive provisions in 40 CFR 403.13, that factors relating to its discharge are fundamentally different from the factors considered by EPA when developing the categorical pretreatment standard.
(4) A user may obtain a net gross adjustment to a categorical standard in accordance with 40 CFR 403.15.
(c) State Pretreatment Standards (RESERVED).
(d) Local Limits.
(1) No industrial user shall discharge wastewater containing a mass of any pollutant which, when taken together with the mass of that pollutant discharged by all other industrial users will cause the mass of the pollutant to exceed the mass of that pollutant specified in the Headworks Industrial Allowance which has been approved by the Approval Authority for the POTW into which the industrial user discharges.
(2) MACM may establish local limits regulating the discharge of specific pollutants by industrial users. Discharging any pollutant in excess of a local limit or an industrial user's permit shall constitute a violation of this article.
(e) MACM's Right of Revision. MACM reserves the right to establish, by ordinance or in wastewater discharge permits, more stringent standards or requirements on discharges to the POTW.
(f) Dilution. No user shall ever increase the use of process water, or in any way attempt to dilute a discharge, as a partial or complete substitute for adequate treatment to achieve compliance with a discharge limitation unless expressly authorized by an applicable pretreatment standard or requirement. MACM may impose mass limitations on users who are using dilution to meet applicable pretreatment standards or requirements, or in other cases when the imposition of mass limitations is appropriate.
(Ord. 3214. Passed 4-16-01.)