(a) All private hydrants shall have an approved shut-off valve installed in the fire hydrant lead not more than 100 feet from the fire hydrant. Such shut-off valve shall be accessible at all times.
(b) Kennedy, Mueller or equal as approved by the City, six-inch (6") minimum barrel, must be installed on all mains.
(c) Hydrant outlets: Cleveland Standard Threads.
(1) One 5" Integral Storz Pumper Connection.
(2) Two 2½ outlets, 3.066" minimum, eight threads per inch; 3.078" maximum, eight threads per inch.
(Ord. 2015-95. Passed 7-2-15.)