1371.04 HYDRANT STANDARDS.
   (a)   All private hydrants shall have an approved shut-off valve installed in the fire hydrant lead not more than 100 feet from the fire hydrant. Such shut-off valve shall be accessible at all times.
   (b)   Kennedy, Mueller or equal as approved by the City, six-inch (6") minimum barrel, must be installed on all mains.
   (c)   Hydrant outlets: Cleveland Standard Threads.
      (1)   One 5" Integral Storz Pumper Connection.
      (2)   Two 2½ outlets, 3.066" minimum, eight threads per inch; 3.078" maximum, eight threads per inch.