(A) Plans for fire sprinkler system, fire alarm system, a kitchen hood suppression system and high-piled storage arrangements shall be submitted for review to the city’s Building and Planning Departments for review by the Westfield Fire Department Fire and Life Safety Division.
(B) Each applicable submittal must contain the following information:
(1) Sprinkler/standpipe systems:
(a) Accurate shop drawings of the system;
(b) Hydraulic calculations;
(c) Product specification sheets; and
(d) State of Indiana construction design release if required by 675 I.A.C. 12-6.
(2) Fire alarm systems:
(a) Accurate shop drawings of the system;
(b) Battery calculations;
(c) Product specifications; and
(d) State of Indiana construction design release if required by 675 I.A.C. 12-6.
(3) Requirements for kitchen hood fire suppression system submissions:
(a) Hood listing and installation documentation;
(b) Schematic of the fire suppression system installation and protected equipment;
(c) Product specification sheets of the nozzles, tanks, piping, agent and other related items; and
(d) State of Indiana construction design release if required by 675 I.A.C. 12-6.