§ 34.105 REQUIRED WATER SUPPLY FOR FIRE PROTECTION.
   In setting the requirements for fire-flow, the Fire Prevention Chief shall use the provisions set forth in 675 I.A.C. 22, as a guide. Notwithstanding the provisions of this section, a reduction in required fire-flow, of up to 75%, is allowed when the building is provided with an approved automatic sprinkler system. The resulting fire-flow shall not be less than 1,000 gallons per minute at 20 psi residual utilizing one test hydrant and one flow hydrant.