(A) Mobile home parks shall be kept free of litter, rubbish, and other flammable material. Portable fire extinguishers rated for Classes A, B and C fires shall be kept visible in service buildings and at other locations conveniently and readily accessible for use by all of the occupants and shall be maintained in good operation condition. Their capacity shall not be less than 2.5 gallons for Class A extinguishers and 5 pounds carbon dioxide or 10 pounds dry powder for Class B and C extinguishers.
(B) Fire shall be mad only in stoves, incinerators, and other equipment intended for such purposes.
(C) Fire hydrants shall be installed in the park water supply system is capable to serve them in accordance with the following requirements:
(1) The water supply system shall permit the operation of a minimum 1½-inch hose streams.
(2) Fire hydrants, if provided, shall be located within 500 feet of any mobile home, service building, or other structure in the park.
(Ord. 239, § 1212, Am. #4, passed - -2004)