§ 53.03 BUILDING SEWER.
   (A)   The building sewer shall be located at least 50 feet from any water supply well or pump suction line serving a residence; however, sewers constructed of water works grade cast iron having mechanical or push typed joints or of water works grade pressure type plastic with an SDR rating of 26 having gasketed or push type joints may be located within the 50-foot distance, but not closer than 20 feet to dug and bored wells and not closer than ten feet to drilled and driven wells or underground pump suction lines.
   (B)   The building sewer shall be so designed and constructed to give mean velocities, when flowing full, of not less than two feet per second, based on Kutters formula using an “N” value of 0.013.
(1982 Code, § 91.03) (Ord. passed 1-13-1967; Ord. passed 1-22-1979; Ord. passed 4-29-1985; Ord. passed 11-17-1986) Penalty, see § 53.99