1501.13 AMENDMENTS.
   The Ohio Fire Code is hereby amended as follows:
   F-3804.3 Table 3804.3
 
Table 3804.3
SEPARATION FOR TANK CONTAINER SYSTEMS
                        Minimum Distance (in feet)
Water Capacity   Mounded or      Between
Per Container      Underground   Above-   Above-ground
(in Gallons)      (note (D))   ground   Containers
Less than 125      10   None   None
         (Note B)
125 to 250      10   15   None
251 to 500      10   25   10
501 to 2,000      25   50   10
2,001 to 30,000   50   75   10
30,001 to 70,000   50   100   
70,001 to 90,000   50   125   (1/4 of sum of
90,001 to 120,000   50   150   diameters of
            adjacent
            containers)