§ 51.06 POTABLE SPECIFICATIONS.
   The following are potable water specifications:
   (A)   All meters installed by contractor will be Hersey Hot Rod Radio Read (no exceptions);
   (B)   All meters over one inch will be compound;
   (C)   Meter sizes required: three-quarters, one, two, four, six or eight; no one and one-half or three-inch meters allowed;
   (D)   Contractors will do all taps and will provide valves with brass fittings on both sides of road if bore required;
   (E)   All meters one inch and above will require RPZ backflow device above ground;
   (F)   Per state law, some three-quarter-inch services may require backflow protection;
   (G)    Three-quarter-, one- and two-inch require setters;
   (H)   Backflow devices will be on pad and in a hot box to prevent freezing;
   (I)   Meter boxes will be PVC type of the appropriate size;
   (J)   Contractors will call town forces to observe tap;
   (K)   No taps will be done weekdays after 4:00 p.m., on weekends or holidays (town observed);
   (L)   All bores will be encased with steel or ductile iron pipe;
   (M)   Lines will be encased if run across ditches with steel or ductile iron pipe;
   (N)   Gasket joints on DOT ROWs;
   (O)   Lines will be pressure tested and town forces must observe;
   (P)   DENR requirements for disinfection and town to have BacT results before service;
   (Q)   Engineer certification required before service activated;
   (R)   Engineer responsible for inspections; and
   (S)   C900 pipe shall be used.