1115.11 FIRE HYDRANTS.
   The subdivider shall provide fire hydrants within all subdivisions served by public water lines. All fire hydrants shall be located between the back of curb and individual property lines. Further, fire hydrants shall be spaced at intervals not to exceed 300 feet. All fire hydrants shall have a minimum main valve opening of five inches and shall have a four-inch pumper connection and two (2), two and one-half-inch hose connections, and shall be designed in accordance with the construction and materials specifications standards specified by the City Engineer and Director of Public Works and the County Sanitary Engineering Department.
(Ord. 2-99. Passed 1-19-99.)