§ 157.382 FIRE PROTECTION.
   (A)   Parks shall be kept free of all liter, rubbish, or other accumulated flammable materials. Inoperable or unlicensed vehicles are prohibited.
   (B)   If the park is served by a public water system, approved fire hydrants shall be located throughout the park and shall be located not more than 500 feet from any manufactured/mobile home. The hydrants shall deliver a minimum of 75 gallons of water per minute at a pressure of 20 pounds per square inch at the highest elevation point of the park.
   (C)   Fire extinguishers shall be provided in accordance with the state’s Department of Public Health requirements.
(Prior Code, 7 TCC 1-22(h))