915.11 BOOSTER PUMPS.
   (a)   Where a domestic or fire booster pump has been installed on the service line to or within any premises, said pump shall be equipped with a low pressure cut-off device to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to ten (10) pounds per square inch gauge or less.
   (b)   The low pressure cut-off device shall be installed, tested and maintained in a manner acceptable to the Director of Sanitary Sewer Services.
(Res. 92-824. Approved 12-29-92; Ord. 2015-555. Adopted 12-14-15.)