9-5-2-10: ROOF-CEILING CONSTRUCTION:
AMENDMENT TO SECTION R-801
GENERAL
   A.   Subsection R-801.3 Roof drainage:
   Add sentence: All downspouts shall discharge onto splash blocks or other material approved by the Building Official.
   B.   Subsection R-801.4 Roof slope:
   R-801.4 Roof slope: All residential structures and additions to existing structures shall have a roof pitch of 3-12 or greater.
   Exceptions:
      1.   Factory manufactured sunrooms with metal or rubber roof systems.
      2.   Additions to existing structures where the existing roof pitch is less than 3-12 with the approval of the Building Official.
AMENDMENT TO SECTION R-802
WOOD ROOF FRAMING
   A.   Subsection R-802.11 Roof tie-down:
   Add sentence: Hurricane anchors shall be used to tie all trusses to exterior walls in all structures.
   Add Exception: Detached accessory structures.
AMENDMENT TO SECTION R-803
ROOF SHEATHING
   A.   Subsection R-803.2.1 Identification and grade:
   Add sentence: Roofs shall be constructed of a minimum of 1/2" thick, 3-ply CDX plywood. Chipboard (OSB)or particleboard shall not be used in roof applications.
   B.   Subsection R-803.2.1.1 Exposure durability:
   Add sentence: Particleboard shall not be used for roof sheathing.
(Ord. 2015-11, 5-21-2015; amd. Ord. 2021-18, 10-21-2021)