§ 51.51  LOCAL LIMITS.
   (A)   An industrial waste survey is required prior to a user discharging wastewater containing in excess of the following average discharge limits:
250 mg/l
BOD
250 mg/l
TSS
40 mg/l
TKN
0.003 mg/l
arsenic
0.003 mg/l
cadmium
0.061 mg/l
copper
0.015 mg/l
cyanide
0.049 mg/l
lead
0.0003 mg/l
mercury
0.021 mg/l
nickel
0.005 mg/l
silver
0.05 mg/l
total chromium
0.175 mg/l
zinc
 
   (B)   (1)   Industrial waste survey information will be used to develop user-specific local limits when necessary to ensure that the POTW’s maximum allowable headworks loading is not exceeded for particular pollutants of concern. User-specific local limits for appropriate pollutants of concern shall be included in wastewater permits.
      (2)   The POTW Director may impose mass limits in addition to, or in place of, the concentration-based limits above.
(Ord. 2007-13, passed 11-6-2012)