§ 9-311 BACKFLOW/BACKSIPHONAGE PREVENTION; FIRE SUPPRESSION SYSTEM.
   1.   All proposed installations of fire suppressions systems shall be reviewed by the Manager to determine the appropriate type of backflow prevention device(s) required.
   2.   All proposed fire suppression systems requiring an antifreeze solution shall use a pharmaceutical grade antifreeze. The consumer shall provide to the Manager a certification identifying the type of pharmaceutical grade antifreeze which shall be used. A double check valve backflow prevention device shall be installed in an approved manner.
   3.   A double check valve of an approved type shall be installed on all proposed fire suppressions systems not utilizing antifreeze, but this may be done only when there are no other cross connections.
   4.   All existing fire suppressions systems shall meet the requirements of subsections (2) or (3) above, whichever applies. An inspection by a certified fire suppression specialist shall be done to determine whether pharmaceutical grade antifeeze(s) have been utilized. This shall be done at the expense of the consumer. If it can not be certified that only pharmaceutical grade antifreezes have been used, then a reduced pressure principle backflow prevention device shall be installed as approved by the Manager. This also shall be done at the expense of the consumer.
   5.   In the event cross connections, such as those found in using auxiliary water supply systems or in providing other water additives such as foaming agents are necessary for the proper operation of the fire suppression system, then a reduced pressure zone backflow prevention device shall be installed in an approved manner.