All new and existing oil storage plants, lumber yards, amusement or exhibition parks, and educational or institutional buildings and similar occupancies and uses involving high fire, or life hazards, and which are located more than 300 feet from a public fire hydrant or which require quantities of water beyond the fire suppression capabilities of the City's water distribution system shall be provided with properly placed fire hydrants. Such fire hydrants shall be capable of supplying fire flows as required by the Fire Official and shall be connected to a water system in accordance with the accepted engineering practice standards listed in this Fire Prevention Code . The Fire Official shall designate and approve the number and location of such fire hydrants. Such fire hydrants shall not be placed into or removed from service until approved by the Fire Official.
(Ord. 06-303. Passed 8-8-06.)