913.08 BOOSTER PUMPS.
   (a)   No person shall install or maintain a water service connection to any premises where a booster pump has been installed on the service line to or within such premises, unless such booster pump is equipped with a low-pressure cutoff designed to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to ten pounds per square inch gauge or less.
 
   (b)   It shall be the duty of the water consumer to maintain the low-pressure cutoff device in proper working order and to certify to the Service Director, at least once a year, that the device is operable.
 
   (c)   The low-pressure cutoff control for booster pumps shall conform to the Ohio E.P.A. Specifications as described in the Ohio E.P.A. publication, Backflow Prevention and Cross-Connection Control, third edition 1987.
(Ord. 89-21. Passed 1-10-89.)