(A) All water main plans and installations, including all appurtenances thereto, shall conform to The Standard Specifications for Water and Sewer Main Construction in Illinois, as established by the State Society of Professional Engineers.
(B) Water distribution facilities including all pipe, fittings, hydrants, valves, vaults and the like, shall be installed to serve all properties within the subdivision.
(C) Where water mains of larger capacity than necessary to serve the subdivision as delineated in the preliminary plan are required to serve the future growth in the vicinity of the subdivision, as determined by the Village Board, the village shall then reimburse the difference in cost of the smaller size and the larger size pipe; the larger size to be determined by the Village Board.
(D) The construction of the water system shall conform to the approved plans and specifications and all work shall be properly inspected and approved by the Village Engineer. Water service line shall be extended to each lot in the subdivision prior to the village accepting the streets for maintenance.
(E) Fire hydrants shall be located and installed by the subdivider with the approval of the Fire Chief, as part of the water distribution system. Installation of hydrants shall be accomplished in such a manner that each lot is within 400 feet of the fire hydrant when measured along the center line of the right-of-way. No fire hydrant shall be placed on a main smaller than six inches in diameter. Hydrants installed shall be of the type approved by the Chief of the Fire Department.
(1994 Code, § 34-3-10)