(A) The Fire Department Connection (FDC) shall not be located more than 50 feet from the nearest hydrant. The FDC shall be located a minimum 1-1/2 times outside the collapse zone of the building.
(B) The FDC shall meet the NFPA requirements.
(C) The FDC shall be provided with a single 5-inch Storz connection that shall face towards the nearest point of Fire Department access.
(D) A minimum 4-inch FDC service pipe shall be utilized on a fire service line that is six inches or larger.
(E) FDC and fire lane signs shall be constructed out of a material that is not susceptible to degradation and have reflective lettering with contrasting red background.