§ 151.048 BELOW GRADE CRAWLSPACES.
   Below-grade crawlspaces are allowed subject to the following standards as found in FEMA Technical Bulletin 11, Crawlspace Construction for Buildings Located in Special Flood Hazard Areas. Residents should note that there is an increased cost for flood insurance associated with below-grade crawlspaces. There is a charge added to the basic policy premium for a below-grade crawlspace versus a standard, at grade, crawlspace foundation.
   (A)   The building must be designed and adequately anchored to resist flotation, collapse, and lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy. Hydrostatic loads and the effects of buoyancy can usually be addressed through the required openings stated in division (B) of this section. Because of hydrodynamic loads, crawlspace construc-tion is not allowed in areas with flood velocities greater than five feet per second unless the design is reviewed by a qualified design professional, such as a registered architect or professional engineer. Other types of foundations are recommended for these areas.
   (B)   The crawlspace is an enclosed area below the base flood elevation (BFE) and, as such, must have openings that equalize hydrostatic pressures by allowing the automatic entry and exit of floodwaters. The bottom of each flood vent opening can be no more than one foot above the lowest adjacent exterior grade.
   (C)   Portions of the building below the BFE must be constructed with materials resistant to flood damage. This includes not only the foundation walls of the crawlspace used to elevate the building, but also any joists, insulation, or other materials that extend below the BFE. The recommended construction practice is to elevate the bottom of joists and all insulation above BFE.
   (D)   Any building utility systems within the crawlspace must be elevated above BFE or designed so that floodwaters cannot enter or accumulate within the system components during flood conditions. Ductwork, in particular, must either be placed above the BFE or sealed from floodwaters.
   (E)   The interior grade of a crawlspace below the BFE must not be more than two feet below the lowest adjacent exterior grade.
   (F)   The height of the below-grade crawlspace, measured from the interior grade of the crawlspace to the top of the crawlspace foundation wall must not exceed four feet at any point. The height limitation is the maximum allowable unsupported wall height according to the engineering analyses and building code requirements for flood hazard areas.
 
   (G)   There must be an adequate drainage system that removes floodwaters from the interior area of the crawlspace. The enclosed area should be drained within a reasonable time after a flood event. The type of drainage system will vary because of the site gradient and other drainage characteristics, such as soil types. Possible options include natural drainage through porous, well-drained soils and drainage systems such as perforated pipes, drainage tiles or gravel or crushed stone drainage by gravity or mechanical means.
   (H)   The velocity of floodwaters at the site should not exceed five feet per second for any crawlspace. For velocities in excess of five feet per second, other foundation types should be used.
(Ord. 259, passed 3-17-2011; Ord. 286, passed 12-7-2017) Penalty, see § 151.999