§ 54.60 GENERAL PROHIBITIONS.
   (A)   No user shall contribute or cause to be contributed, directly or indirectly, any pollutant or wastewater which will interfere with the operation or performance of the POTW. These general prohibitions apply to all the users of a POTW whether or not the user is subject to national categorical pretreatment standards or any other national, state, or local pretreatment standards or requirements. A user may not contribute the following substances to any POTW:
      (1)   Any liquids, solids, or gases which, because of their nature or quantity, are or may be sufficient, either alone or by interaction with other substances, to cause fire or explosion or be injurious in any other way to the POTW or to the operation of the POTW. At no time shall any single reading on an explosion hazards meter at the point of discharge into the system or at any point in the system be more 20% of the lower explosive limit (LEL) of the meter. Prohibited materials include but are not limited to gasoline, kerosene, naphtha, benzene, toluene, xylene, ethers, alcohols, ketones, aldehydes, peroxides, chlorates, perchlorates, bromates, carbides, hydrides, and sulfides, and any other substance which is a fire hazard or a hazard to the system;
      (2)   Solid or viscous substances which may cause obstruction to the flow in a sewer or other interference with the operation of the wastewater treatment facilities, such as but not limited to grease, garbage with particles greater than one-half inch in any dimension, animal guts or tissues, paunch manure, bones, hair, hides, or fleshing, entrails, whole blood, feathers, ashes, cinders, sand, spent lime, stone or marble dust, metal, glass, straw, shavings, grass clippings, rags, spent grains, spent hops, wastepaper, wood, plastics, gas, tar, asphalt residues, residues from refining or processing of fuel or lubricating oil, mud, or glass grinding or polishing wastes;
      (3)   Any wastewater having a pH less than 5.5 or greater than 9.5, or wastewater having any other corrosive property capable of causing damage or hazard to structures, equipment, and/or personnel of the POTW;
      (4)   Any wastewater containing toxic pollutants in sufficient quantity, either singly or by interaction with other pollutants, to injure or interfere with any wastewater treatment process, constitute a hazard to humans or animals, create a toxic effect in the receiving waters of the POTW, or to exceed the limitation set forth in a categorical pretreatment standard. A toxic pollutant shall include but not be limited to any pollutant identified pursuant to § 307(a) of the Act;
      (5)   Any noxious or malodorous liquids, gases, or solids which, either singly or by interaction with other wastes, are sufficient to create a public nuisance or hazard to life or are sufficient to prevent entry into the sewers for maintenance and repair;
      (6)   Any substance which may cause the POTW’s effluent or any other product of the POTW, such as residues, sludges, or scums, to be unsuitable for reclamation and reuse or to interfere with the reclamation process. In no case shall a substance discharged to the POTW cause the POTW to be in noncompliance with sludge use or disposal criteria, guidelines, or regulations developed under § 405 of the Act; any criteria, guidelines, or regulations affecting sludge use or disposal developed pursuant to the Solid Waste Disposal Act, the Clean Air Act, the Toxic Substances Control Act; or state criteria applicable to the sludge management method being used;
      (7)   Any substance which will cause the POTW to violate its NPDES and/or state disposal system permit or the receiving water quality standards;
      (8)   Any wastewater with objectionable color not removed in the treatment process, such as but not limited to dye wastes and vegetable tanning solutions;
      (9)   Any wastewater having a temperature which will inhibit biological activity in the POTW treatment plant resulting in interference, but in no case wastewater with a temperature at the introduction into the POTW which causes the treatment plant influent to exceed 104ºF;
      (10)   Any pollutants, including oxygen demanding pollutants (BOD and the like) released at a flow rate or pollutant concentration that a user knows or has reason to know will cause interference to the POTW. In no case shall a slug load have a flow rate or contain concentration or qualities of pollutants that exceed, for any time period longer than 15 minutes, more than five times the user’s average 24-hour concentration, quantities, or flow during normal operation;
      (11)   Any wastewater containing any radioactive wastes or isotopes of a half-life or concentration that may exceed limits established by the Superintendent in compliance with applicable state or federal regulations; or
      (12)   Any wastewater which causes a hazard to human life or creates a public nuisance.
   (B)   When the Superintendent determines that a user is contributing to the POTW any of the above substances enumerated in division (A) of this section in such amounts as to interfere with the operation of the POTW, the Superintendent shall:
      (1)   Advise the user of the impact of the contribution on the POTW; and
      (2)   Develop effluent limitations for the user to correct the interference with the POTW.
(Ord. 02-03, passed 7-15-2002)