25.03.26: AMENDMENT OF SECTION R1001.3.1:
Notwithstanding the provisions of section 25.03.01 of this article, section R1001.3.1 of the Residential Code is amended to read as follows:
   R1001.3.1Vertical reinforcing. For chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars adequately anchored into the concrete foundation shall be placed between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section R609. Grout shall be prevented from bonding with the flue liner so that the flue liner is free to move with thermal expansion. For chimneys more than 40 inches (1016 mm) wide, two additional No. 4 vertical bars adequately anchored into the concrete foundation shall be provided for each additional flue incorporated into the chimney or for each additional 40 inches (1016 mm) in width or fraction thereof.
(Ord. 0-19-1357, 11-13-2019)