25.03.23: AMENDMENT OF SECTION R606.12.2.2.3:
Notwithstanding the provisions of Section 25.03.01 of this article, section R606.12.2.2.3 of the Residential Code is amended to read as follows:
   R606.12.2.2.3 Reinforcement requirements for masonry elements. Masonry elements listed in Section R606.12.2.2.2 shall be reinforced in either the horizontal or vertical direction as shown in Figure R606.11(3) and in accordance with the following:
   1.   Horizontal reinforcement. Horizontal joint reinforcement shall consist of at least one No. 4 bar spaced not more than 48 inches (1219 mm).Horizontal reinforcement shall be provided within 16 inches (406 mm) of the top and bottom of these masonry elements.
   2.   Vertical reinforcement. Vertical reinforcement shall consist of at least one No. 4 bar spaced not more than 48 inches (1219 mm). Vertical reinforcement shall be within 8 inches (406mm) of the ends of masonry walls.
(Ord. 0-19-1357, 11-13-2019)