Damaged structures of all occupancies regulated by the County of San Bernardino which have been damaged as a result of a disaster shall be repaired in accordance with the following criteria:
(a) When the estimated value of repair does not exceed ten percent of the replacement value of the structure, the damaged portion(s) shall be restored to their predisaster condition.
(b) When the estimated value of repair is greater than ten percent, but less than 50 percent, of the replacement value of the structure, the damaged elements, as well as all critical ties associated with those elements, shall be repaired and/or brought into conformance with the structural requirements of the current Code.
(c) When the estimated value of repair exceeds 50 percent of the replacement value of the structure, the entire structure shall be brought into conformance with the structural requirements of the current Code.
(d) Exception: The repair of damaged chimneys in Group R, Division 3 occupancies shall be excluded from the computation of percentage of replacement value and chimneys shall be repaired pursuant to § 63.1125.
(Ord. 3501, passed - -1992)