The quantity of water available from all water sources and distribution storage reservoirs shall at least equal those amounts shown in Tables I and II of the Article.
(Ord. 2518, passed - -1981; Am. Ord. 2537, passed - -1981; Am. Ord. 2670, passed - -1982; Am. Ord. 2701, passed - -1982; Ord. 3105, passed - -1986; Am. Ord. 3512, passed - -1992; Am. Ord. 3516, passed - -1992; Am. Ord. 3659, passed - -1996)
TABLE I GRAVITY STORAGE SYSTEM SOURCE AND STORAGE CAPACITY | ||||||
Minimum Use | Median Use | High Use |
TABLE I GRAVITY STORAGE SYSTEM SOURCE AND STORAGE CAPACITY | ||||||
Minimum Use | Median Use | High Use | ||||
Recreational Dwelling with No Irrigation | Typical or Average Residence and Lot | Residence With Large Lot | ||||
No. of Service Connections | Source Capacity (gpm) | Storage Capacity (gals) | Source Capacity (gpm) | Storage Capacity (gals) | Source Capacity (gpm) | Storage Capacity (gals) |
10 | 11 | 3,500 | 17 | 4,000 | 28 | 4,900 |
20 | 19 | 6,900 | 32 | 7,800 | 53 | 9,600 |
30 | 26 | 10,100 | 45 | 11,400 | 75 | 14,130 |
40 | 33 | 13,100 | 57 | 14,800 | 95 | 18,400 |
50 | 40 | 15,900 | 69 | 18,000 | 115 | 22,500 |
60 | 46 | 18,500 | 80 | 21,000 | 134 | 26,400 |
70 | 52 | 20,900 | 90 | 23,800 | 151 | 30,200 |
80 | 58 | 23,100 | 100 | 25,400 | 167 | 33,900 |
90 | 64 | 25,100 | 109 | 27,800 | 181 | 37,500 |
100 | 69 | 27,000 | 117 | 30,100 | 195 | 41,000 |
120 | 74 | 30,500 | 133 | 34,500 | 220 | 47,700 |
140 | 79 | 33,600 | 149 | 38,900 | 245 | 54,000 |
160 | 84 | 36,400 | 165 | 43,300 | 270 | 59,900 |
180 | 89 | 39,200 | 181 | 47,700 | 295 | 65,400 |
200 | 94 | 42,000 | 197 | 52,200 | 320 | 70,500 |
Source and Storage Design Guide for Small Water Systems, State of California, State Department of Health, Water Sanitation Section, 1967. | ||||||
TABLE II PRESSURE TANK SYSTEM SOURCE CAPACITY | |||
Minimum Use | Median Use | High Use |
TABLE II PRESSURE TANK SYSTEM SOURCE CAPACITY | |||
Minimum Use | Median Use | High Use | |
Recreational Dwelling with No Irrigation | Typical or Average Residence and Lot | Residence with Large Lot | |
No. of Service Connections | Source Capacity (gal per minute) | Source Capacity (gal per minute) | Source Capacity (gal per minute) |
10 | 40 | 50 | 69 |
20 | 77 | 97 | 133 |
30 | 110 | 140 | 193 |
40 | 142 | 180 | 248 |
50 | 174 | 219 | 302 |
60 | 200 | 255 | 354 |
70 | 226 | 288 | 403 |
80 | 251 | 312 | 449 |
90 | 273 | 341 | 494 |
100 | 294 | 367 | 537 |
120 | 328 | 420 | 618 |
140 | 363 | 473 | 695 |
160 | 387 | 526 | 770 |
180 | 416 | 579 | 840 |
200 | 444 | 630 | 908 |
Source and Storage Design Guide for Small Water Systems, State of California, State Department of Health, Water Sanitation Section, 1967. | |||