Prior to the issuance of the certificate of occupancy for a newly-constructed, renovated, remodeled or change of occupancy of a Class 1 Structure, the Fire Department is required to witness a successful acceptance or performance test in accordance with the appropriate installation standard or manufacturer's specifications for the following systems:
(A) Fire alarm system;
(B) Sprinkler and standpipe system;
(C) Special hazard fire suppression system;
(D) Private fire service underground piping hydrostatic test and flush;
(E) Fire pump;
(F) Smoke control system;
(G) Above-ground piping hydrostatic test;
(H) Emergency lighting system;
(I) Underground storage tank tightness test; and
(J) Grease duct leakage test (Type 1 Hood Exhaust System).