Plans for fire alarms systems, water-based fire protection systems, fire pumps, special hazard fire suppression systems, high-piled storage arrangements and firestop systems shall be submitted to the Fire Chief or his or her designee prior to the request for a required wall rough inspection. Each respective submittal shall contain the following information;
(A) Sprinkler systems:
(1) One full set of sprinkler/standpipe plans;
(2) One full set of sprinkler/standpipe calculations;
(3) One copy of the sprinkler construction design release (CDR); and
(4) One set of manufacturer's cut-sheets for all sprinkler heads in the design.
(B) Fire alarm systems:
(1) One full set of fire alarm plans (1/8" - 1' scale);
(2) One set of battery calculations;
(3) One copy of the fire alarm construction design release (CDR);
(4) One set of manufacturer's cut-sheets for the fire alarm control panel (FACP) and fire alarm components; and
(5) One fire alarm performance matrix.
(C) Special hazard fire protection systems:
(1) One set of plans (if applicable);
(2) One set of engineering data (if applicable);
(3) One copy of the construction design release (if applicable); and
(4) One set of manufacturer's cut-sheets for system components.
(D) Fire pumps:
(1) One copy of the manufacturer's fire pump specifications; and
(2) One copy of the manufacturer's certified pump test characteristic curve.
(E) Firestop systems:
(1) Through-penetration firestop systems;
(2) Membrane-penetration firestop systems;
(3) Fire-resistant joint systems;
(4) Perimeter fire barrier systems; and
(5) Fire-rated duct and air-transfer openings.
(Ord. 2017-35, passed 12-19-2017)