§ 50.19 SERVICE PIPE.
   (A)   The water service pipe shall run in as direct a line as possible between water main to parkway stopcock to meter, and shall be approximately five feet below ground level with no branches taken off between main and meter. The service pipe shall extend above the basement floor if meter is in the basement, above the building floor if meter is in building or above the vault floor if the meter is in an outside vault. The service pipe must be of copper, type k, of weight and size as prescribed in the village plumbing code, but no less than ¾-inch internal diameter except that where the service pipe is more than two inches in diameter it may be ductile iron. It shall be equipped with a shutoff both at the parkway and at the meter.
   (B)   All buildings connected to the village water distribution shall be serviced by service pipes meeting the following requirements:
Residential      1-inch maximum internal diameter
Commercial      1-inch minimum internal diameter
Industrial      3-inch minimum internal diameter
('71 Code, Ch. 13 § l-10) (Ord. 192, passed ll-5-58; Am. Ord. 267, passed 11-15-67; Am. Ord. 316, passed 7-21-71; Am. Ord. 22-1762, passed 3-16-22)