§ 91.54 SPRINKLER SYSTEM SUPERVISION AND PROTECTION.
   Valves controlling fire sprinkler systems shall be supervised open by the following:
   (A)   Chained and locked in open position; keys for the locks shall be provided to the Fire Department to be placed in the rapid entry key box.
   (B)   A local audible alarm at the fire alarm control panel, and annunciators (if equipped) with transmission of a trouble signal to Fire Department dispatch center.
   (C)   Sprinkler risers and banks located in open areas shall be protected from damage to include possible collision with vehicles.
(Ord. 05-0251, passed 3-16-05; Am. Ord. 11-0923, passed 9-21- 11; Am. Ord. 11-0935, passed 11- 2-11; Am. Ord. 12-1016, passed 11-7-12; Am. Ord. 17-1347, passed 3-1-17; Am. Ord. 22-1811, passed 12-7-22)