§ 154.553 STORAGE.
   (A)   The open storage of materials and equipment shall, except for sales display, be subject to the following requirements:
      (1)   Storage of materials and equipment shall be completely screened from view. An eight-foot solid wall fence with a level A bufferyard as described in §§ 154.590 through 154.599 will be required; and
      (2)   All combustible material shall be stored in such a way as to include, where necessary, access drives to permit free access of firefighting equipment.
   (B)   (1)   The bulk storage of flammable liquids and chemicals, when stored in aboveground tanks, shall occur no closer than the lot line or any principle building than the distance indicated by the following table:
Capacity per Container (Gallons)
Minimum Separation Distances Aboveground Containers
Capacity per Container (Gallons)
Minimum Separation Distances Aboveground Containers
Less than 125
None
125 to 250
10 feet
251 to 500
10 feet
501 to 2,000
25 feet
2,001 to 30,000
50 feet
30,001 to 70,000
75 feet
70,001 to 90,000
100 feet
 
      (2)   The distance may be reduced to not less than ten feet for a single container of 1,200 gallons capacity or less, provided such a container is at least 25 feet from any other container or more than 125 gallons capacity.
   (C)   The underground bulk storage of flammable liquids shall be located in accordance with the Uniform Fire Code regarding tank storage underground, except the minimum distance between such underground tanks and any R Zone boundary shall be at least ten feet.
(Ord. passed 5-16-2023)