§ 154.095 WATER MAIN SUPPLY SYSTEM.
   (A)   For all proposed developments within the village or to be annexed to the village, the developer shall provide the development with a complete water main supply system which shall be connected to the municipal water supply subject to there being capacity within the municipal system to serve that development.
   (B)   If connection to the village system is not reasonable or feasible, the developer shall provide a complete water main supply system connected to a public water supply system approved by the State Department of Public Health and IEPA with satisfactory provision for the operation and maintenance thereof.
   (C)   No individual or private water supply shall be allowed in commercial developments without approval from the village and approval from the Village Engineer.
   (D)   Water mains shall be of a type as specified by the village or as approved by the Village Engineer.
   (E)   Water mains shall be a minimum of six inches in diameter. Larger size water mains shall be provided if required to adequately serve the proposed development. If larger size mains are required by the village to serve areas other than the proposed development, the cost difference may be paid by the village in accordance with any such policies in effect at the time the development is considered. When PVC water main pipe is used, tracer wire (thin, soft drawn, solid No. 12 copper) shall be installed, as a minimum, directly on the water main every 20 feet and brought to the surface at valves and hydrants. Deflections of the water main greater than 11.25 degrees shall be thrust protected with either thrust restraints or restrained joint pipe. When the water main connections are required that involve two different pipe materials, the connection shall be made with a Model 3501 Transition Coupling by PowerSal Engineering or approved equal.
   (F)   Village standard fire hydrants shall be provided at a maximum spacing of 600 feet. The location of the hydrants shall be at lot lines and at block corners. Village standard fire hydrants shall be Mueller Co. Centurion steamer type with two two and one-half inch standard nozzles, one four and one-half inch pumper nozzle, five and one-fourth inch barrel and painted yellow.
    (G)   Village standard fire hydrants shall be provided at a maximum spacing of 600 feet. The location of the hydrants shall be at lot lines and at block corners. Village standard fire hydrants shall be Mueller Co. Centurion steamer type with two two and one-half inch standard nozzles, one four and one-half (4 Viz) inch pumper nozzle, five and one-fourth inch barrel and painted a color choice of the Village.
   (H)   The water mains shall be located generally on the south and west sides of streets, between the sidewalk and curb with a minimum cover of four feet zero inches.
   (I)   All water main crossings of streets shall be backfilled with FA-6 select granular backfill and mechanically compacted in eight inch lifts to a point five feet behind the curb.
   (J)   All water main construction shall be performed in accordance with the Standard Specifications for Water and Sewer Main Construction in Illinois, latest edition.
   (K)   An individual water service shall be installed for each lot or parcel in the development.
    (L)   The meter pit shall be installed three feet from the sidewalk, on the commercial and industrial property side. Single service water meter pits shall be 18-inch diameter PVC and 24-inch diameter PVC for double service meter pits. Each meter box shall have a cover labeled “WATER METER” on the lid and shall be Model No. H-10810 by Mueller Co. Meter connections shall be Mueller Co. B2404 R2-583415 Yoke with H-14227 compression connections at each end. Meters are to be provided and installed by the village.