1347.05 "EARTH STATION" SUPPORT STRUCTURES.
   (a)    Only metal support, galvanized construction, or equal thereto, shall be allowed.
   (b)    Only a concrete base or caissons, depending on soil conditions, shall be employed in line with grade.
   (c)    The structure shall be designed to withstand wind force of up to eight-five miles per hour in a manner conforming with good engineering practices.
   (d)    Any driving motor shall be limited to 110V maximum power design and shall be encased in protective guards.
   (e)    All underground electrical wiring must be encased in rigid conduit with eighteen inch cover. Any overhead wiring must also meet the approval of the Electrical Inspector.
   (f)    The "earth station" must be bonded to an eight-foot grounding rod.
   (g)    If guy lines are to be used, they must be confined within a screened area.
   (h)    Plans must meet all engineering practices and conform to the Building Code of the City.