In all Special Flood Hazard Areas the following provisions are required:
(A) All new construction and substantial improvements shall be adequately anchored to prevent flotation, collapse, or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy;
(B) Manufactured homes shall be anchored to prevent flotation, collapse, or lateral movement. Methods of anchoring may include, but are not limited to, use of over-the-top or fame ties to ground anchors. This standard shall be in addition to and consistent with applicable state requirements for resisting wind forces.
(C) All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage;
(D) New construction and substantial improvements shall be constructed by methods and practices that minimize flood damage;
(E) Electrical, heating, ventilation, plumbing, air condition equipment, and other service facilities shall be designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding; and if
(F) Within Zones AH or AO, so that there are adequate drainage paths around structures on slopes to guide flood waters around and away from proposed structures.
(G) New and replacement water supply systems shall be designed to minimize or eliminate infiltration of flood waters into the system;
(H) New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of flood waters into the systems and discharges from the systems into flood waters;
(I) On-site waste disposal systems shall be located and constructed to avoid impairment to them or contamination from them during flooding; and,
(J) Any alteration, repair, reconstruction, or improvements to a structure, which is not in compliance with the provisions of this chapter shall meet the requirements of "new construction" as contained in this chapter;
(K) Any alteration, repair, reconstruction, or improvements to a structure, which is not in compliance with the provisions of this chapter, shall be undertaken only if said non-conformity is not furthered, extended, or replaced.
(L) Prohibited uses.
(1) Storage or processing of materials that are hazardous, flammable, or explosive in the identified special flood hazard area.
(2) Storage of material or equipment that, in time of flooding, could become buoyant and pose an obstruction to flow in identified floodway areas.
(3) Storage of material or equipment not otherwise prohibited shall be firmly anchored to prevent flotation.
(Ord. 17-31, passed 12-12-17)