(A) Table B105.2 of the 2022 California Fire Code is hereby amended to read as follows:
Automatic Sprinkler System (Design Standard) | Minimum Fire-Flow (gallons per minute) | Flow Duration (hours) |
No automatic sprinkler system | Value in Table B105.1(2) | Value in Table B105.1(2) |
Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2)a | Duration in Table B105.1(2) at the reduced flow rate |
Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2)b | Duration in Table B105.1(2) at the reduced flow rate |
(a) The reduced fire-flow shall be not less than 1,000 gallons per minute.
(b) The reduced fire-flow shall be not less than 1,500 gallons per minute.