§ 8.24 APPENDIX B: FIRE FLOW REQUIREMENTS FOR BUILDINGS.
   (A)   Table B105.2 of the 2022 California Fire Code is hereby amended to read as follows:
 
Automatic Sprinkler System (Design Standard)
Minimum Fire-Flow (gallons per minute)
Flow Duration (hours)
No automatic sprinkler system
Value in Table B105.1(2)
Value in Table B105.1(2)
Section 903.3.1.1 of the California Fire Code
50% of the value in Table B105.1(2)a
Duration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the California Fire Code
50% of the value in Table B105.1(2)b
Duration in Table B105.1(2) at the reduced flow rate
 
      (a)   The reduced fire-flow shall be not less than 1,000 gallons per minute.
      (b)   The reduced fire-flow shall be not less than 1,500 gallons per minute.