§ 8.20 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.
   (A)   § 3310.1 of the 2022 California Fire Code is hereby added to read as follows:
      (1)   Required access roads shall be capable of supporting imposed loads up to 75,000 pounds shall be maintained during all phases of construction.
      (2)   Buildings under construction shall have approved address numbers, building numbers or approved building identification placed at the entry point of each fire access road.
   (B)   § 3310.1 of the 2022 California Fire Code is hereby added to read as follows:
      (1)   Fire hydrant(s) capable of meeting minimum fire flows of 1,000 gallons per minute shall be charged and available to all sites under construction prior to the stacking of combustible materials on site. Fire hydrants shall be located within 500' of the furthest most point of construction; use of an existing hydrant shall not interfere the with daily routine traffic patterns of city residents.
(Ord. 1055, passed 11-19-2019; Am. Ord. 1070, passed 11-15-2022)