§ 155.30 WATER SYSTEMS PROPOSALS.
   (A)   The requirements of the location of Class I water systems, in order to protect water quality (More than 10 lots):
      (1)   Safe distance from any contaminant source;
      (2)   At least 200 feet from a liquid waste disposal site of less than 1,000 gallons per day;
      (3)   At least 300 feet from a liquid waste disposal site of more than 1,000 gallons per day;
      (4)   At least 150 feet from nonleakproof wastewater lines;
      (5)   At least 25 feet from wastewater lines which are leakproof;
      (6)   At least 75 feet from a perennial stream;
      (7)   At least 100 feet from other contamination sources such as land fills, stock yards, and animal feed lots; and
      (8)   At least 50 feet from an arroyo or other periodic water-carrying channel.
   (B)   Requirements for Class II water systems (less than 10 lots):
      (1)   Safe distance from any contaminant source;
      (2)   At least 100 feet from a liquid waste disposal of less than 1,000 gallons per day;
      (3)   At least 200 feet from a liquid waste disposal of more than 1,000 gallons per day;
      (4)   At least 100 feet from non-leakproof wastewater lines carrying more than 1,000 gallons per day;
      (5)   At least 75 feet from nonleakproof wastewater lines carrying less than 1,000 gallons per day;
      (6)   At least 25 feet from leakproof wastewater lines;
      (7)   At least 75 feet from perennial streams;
      (8)   At least 75 feet from other contamination sources, such as land fills, stock yards, and animal feed lots; and
      (9)   At least 50 feet from arroyos and other periodic water-carrying channels.
(1981 Code, App. B) (Ord. 625, App. A, passed 2-25-1975) Penalty, see § 155.99