§ 51.48 FACILITIES REQUIRING PROTECTION.
   (A)   Approved backflow prevention assemblies shall be installed on the service line to any premises that the Town of Ranlo Water has identified as having a potential for backflow.
   (B)   The following types of facilities or services have been identified by the Town of Ranlo Water as having a potential for backflow of non-potable water into the public water supply system. Therefore, an approved backflow prevention assembly will be required on all such services according to the degree of hazard present. Other types of facilities or services not listed below may also be required to install approved backflow prevention assemblies if determined necessary by the Town of Ranlo Water. As a minimum requirement, all commercial services will be required to install a double check valve assembly, unless otherwise listed in this division.
Legend:
DCVA = Double check valve assembly
RP = Reduced pressure principle assembly
DCDA = Double check detector assembly
RPDA = reduced pressure detector assembly
AG = Air gap
PVB = pressure vacuum breaker
Agricultural meter
RP
Aircraft and missile plants
RP
Automotive plants
RP
Automotive services stations, dealerships and the like
 
   No health hazard
DCVA
   Health hazard
RP
Auxiliary water systems
 
   Approved public/private water supply
DCVA
   Unapproved public/private water supply
AG
   Used water and industrial fluids
RP
Bakeries
 
   No health hazard
DCVA
   Health hazard
RP
Beauty shops/barber shops
 
   No health hazard
DCVA
   Health hazard
RP
Beverage bottling plants
RP
Breweries
RP
Buildings: hotels, apartment houses, public and private buildings, or other structures having unprotected cross connections
 
   (Under five stories) no health hazard
DCVA
   (Under five stories) health hazard
RP
   (Over five stories) all
RP
Canneries, packing houses, and rendering plants
RP
Chemical plants: manufacturing, processing, compounding or treatment
RP
Chemically contaminated water systems
RP
Commercial car-wash facilities
RP
Commercial greenhouses
RP
Commercial sales establishments (department stores, malls, and the like)
 
   No health hazard
DCVA
   Health hazard
RP
Concrete/asphalt plants
RP
Dairies and cold storage plants
RP
Dye works
RP
Film laboratories
RP
Fire systems; fire trucks
 
   Systems ¾ inch to two inches:
 
      No health hazard
DCDA (fire trucks do not require detector assembly.)
      Health hazard (booster pumps, foam, antifreeze solution, and the like)
RP (fire trucks do not require detector assembly.)
   Systems 2 ½ inches to ten inches or larger
 
      No health hazard
DCDA (fire trucks do not require detector assembly
      Health hazard (booster pumps, foam, antifreeze solution, and the like)
RPDA (fire trucks do not require detector assembly.)
Hospitals, medical buildings, sanitariums, morgues, mortuaries, autopsy facilities, nursing and convalescent homes, medical clinics, and veterinary hospitals
RP
Industrial facilities
 
   No health hazard
DCVA
   Health hazard
RP
Laundries
 
   No health hazard
DCVA
   Health hazard (i.e., dry cleaners)
RP
Lawn irrigation systems (split taps)
RP
Metal manufacturing, cleaning, processing, and fabricating plants
RP
Mobile home parks
 
   No health hazard
DCVA
   Health hazard
RP
Oil and gas production, storage or transmission properties
RP
Paper and paper products plants
RP
Pest control (exterminating and fumigating)
RP
Plating plants
RP
Power plants
RP
Radioactive materials or substances plants or facilities handling
RP
Restaurants
 
   No health hazard
DCVA
   Health hazard
RP
Restricted, classified, or other closed facilities
RP
Rubber plants (natural or synthetic)
RP
Sand and gravel plants
RP
Schools and colleges
RP
Sewage and storm drain facilities
RP
Swimming pools
 
   Direct plumbing
RP
   Indirect plumbing
AIR GAP with Pressure Vacuum Breaker on designated spigot for pool.
Waterfront facilities and industries:
RP
 
   (C)   All assemblies and installations shall be subject to inspection and approval by the Town of Ranlo Water.