§ 52.017 LOCAL LIMITS.
   (A)   An industrial waste survey is required prior to a user discharging wastewater containing in excess of the following instantaneous maximum allowable discharge limits.
Milligrams Per Liter
Pollutant
Milligrams Per Liter
Pollutant
0.003
arsenic
0.003
cadmium
0.061
copper
0.041
cyanide
0.049
lead
0.0003
mercury
0.021
nickel
0.005
silver
0.05
total chromium
0.175
zinc
 
   (B)   Industrial waste survey information will be used to develop user-specific local limits when necessary to ensure that the POTW’s maximum allowable headworks loading is not exceeded for particular pollutants of concern. User-specific local limits for appropriate pollutants of concern shall be included in wastewater permits. The POTW Director may impose mass based limits in addition to, or in place of, concentration based limits.