Each premise shall be supplied through a separate shut-off valve that is accessible to the Department of Utilities at all times. The service pipe must have a minimum cover of four and one-half feet and maintain a minimum horizontal separation of ten feet and vertical separation of 18 inches from any sanitary sewer, storm sewer or drain pipe. A licensed, bonded plumber must be employed by the customer to install the customer service line beginning at the outlet of the city’s shut-off valve.