§ 95.047 SMOKE DETECTOR LOCATION REQUIREMENTS.
   (A)   The owner of each single-family dwelling unit shall install at least one smoke detector in the vicinity of the sleeping areas and on every level of the dwelling. If sleeping rooms are not located in the same area or off the same hallway, then more than one smoke detector is required.
   (B)   The owner of each multi-family dwelling unit shall install smoke detectors in either each individual sleeping room or in a corridor that is adjacent to a room used for sleeping but in no case may the smoke detectors be spaced further apart than 30 feet or more than 15 feet from any wall.
   (C)   The owner of each hotel, motel, hospital, nursing home, jail, prison or residential-custodial care facility shall install smoke detectors in both the amount directed by the Town Fire Chief or his or her designee and in the location(s) directed by the Town Fire Chief and his or her designee.
(1991 Draft Code, § 6-112) (Ord. 9-90, passed 5-14-1990) Penalty, see § 95.999