10-2-2-3: ELECTRICAL CODE AMENDMENTS:
The following provisions shall further apply and shall supersede any and all references listed within the 2020 edition of the National Electrical Code (NFPA 70-2020):
   Revise to include Section 250.50(A): Grounding Electrode Systems for New Construction. New buildings or structures shall use a concrete-encased electrode specified in 250.52(A)(3) as the primary grounding electrode system. Where available and installed, grounding electrodes described in 250.52(A)(1) through (A)(7) shall be bonded together to form the grounding electrode system.
(Ord. 2004-01, 1-19-2004; amd. Ord. 2024-O-17, 8-5-2024, eff. 10-1-2024)