(A) The type of protection required shall depend on the degree of hazard which exists as follows:
(1) An approved fixed proper air gap separation shall be installed where the public water supply system may be contaminated with substances that could cause a severe health hazard.
(2) An approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention assembly shall be installed where the public water supply system may be contaminated with a substance that could cause a system or health hazard.
(3) An approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention assembly or a double check valve assembly shall be installed where the public water supply system may be polluted with substances that could cause a pollution hazard not dangerous to health.
(B) The type of protection required under this section shall be an approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention device.
(C) Where a public water supply or an auxiliary water supply is used for a fire protection system, reduced pressure principle backflow preventers shall be installed on fire safety systems connected by the public water supply, when:
(1) The fire safety system contains antifreeze, fire retardant or other chemicals.
(2) Water is pumped into the system from another source.
(3) Water flows by gravity from a non- potable source or water can be pumped into the fire safety system from any other source.
(4) There is a connection whereby another source can be introduced into the fire safety system.
(D) All other fire safety systems connected to the potable water supply shall be protected by a double check valve assembly on unmetered service lines.
(Ord. 0-91-4, passed 12-2-91)