(A) Every owner, manager or agent of any multiple dwelling or of any single or multiple occupancy lease or rental family dwelling unit shall install, in every dwelling unit, not less than one approved smoke detector on the ceiling, not less than six inches from any wall, or on a wall, located from six to 12 inches from the ceiling, and within 15 feet of all rooms used for sleeping purposes.
(Prior Code, § 6-1-5)
(B) Every owner, manager or agent of any multiple dwelling or any single or multiple occupancy lease or rental family dwelling unit shall install not less than one approved smoke detector on the uppermost ceiling of each level, not less than six inches from any wall, or on wall, located from six to 12 inches from the uppermost ceiling of all interior stairwells.
(Prior Code, § 6-1-6)
(Ord. 87-4-1, passed - -)