Exception: The repair or replacement of an existing combined building sewer as of the initial adoption date of this code.
P-1109.3 Size of existing combined building drains and building sewers when adding additional load. The size of a combination sanitary and storm drain or sewer shall be computed in accordance with the method in Table 1109.4. The fixture units shall be converted into an equivalent projected roof or paved area. Where the total fixture load on the combined drain is less than or equal to 256 fixture units, the equivalent drainage area in horizontal projection shall be taken as 4,000 square feet (372 m
2). Where the total fixture load exceeds 256 fixture units, each additional fixture unit shall be considered the equivalent of 15.6 square feet (1.5 m
2) of drainage area. These values are based on a rainfall rate of 6" (127 mm) per hour.
Note: Bring in Table 1106.3 from the 2012 IPC for 6" rainfall rate only
* * *
SIZE OF HORIZONTAL PIPE
|
HORIZONTALLY PROJECTED ROOF AREA (square feet)
|
1/8 unit vertical in 12 units horizontal (1% slope) | |
3 | 548 |
4 | 1,253 |
5 | 2,227 |
6 | 3,566 |
8 | 7,600 |
10 | 13,800 |
12 | 22,200 |
15 | 39,650 |
1/4 unit vertical in 12 units horizontal (2% slope) | |
3 | 773 |
4 | 1,766 |
5 | 3,146 |
6 | 5,033 |
8 | 10,866 |
10 | 19,450 |
12 | 31,350 |
15 | 56,000 |
1/2 unit vertical in 12 units horizontal (4% slope) | |
3 | 1,096 |
4 | 2,500 |
5 | 4,450 |
6 | 7,140 |
8 | 15,320 |
10 | 27,600 |
12 | 44,400 |
15 | 79,250 |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2
* * *