11-1-7: PROTECTING BUILDINGS:
   A.   In addition to the damage prevention requirements of section 11-1-6 of this chapter, all buildings located in the floodplain shall be protected from flood damage below the flood protection elevation. This building protection requirement applies to the following situations:
      1.   Construction or placement of a new building valued at more than one thousand dollars ($1,000.00) or seventy (70) square feet;
      2.   Substantial improvements made to an existing building. This alteration shall be figured cumulatively beginning with any alteration which has taken place subsequent to the adoption of this chapter;
      3.   Repairs made to a substantially damaged building. These repairs shall be figured cumulatively beginning with any repairs which have taken place subsequent to the adoption of this chapter.
      4.   Structural alterations made to an existing building that increase the floor area by more than twenty percent (20%);
      5.   Installing a manufactured home on a new site or a new manufactured home on an existing site (the building protection requirements do not apply to returning a manufactured home to the same site it lawfully occupied before it was removed to avoid flood damage); and
      6.   Installing a travel trailer or recreational vehicle on a site for more than one hundred eighty (180) days per year.
      7.   "Repetitive loss" to an existing building as defined in section 11-1-2 of this chapter.
   B.   Residential or nonresidential buildings can meet the building protection requirements by one of the following methods:
      1.   The building may be constructed on permanent landfill in accordance with the following:
         a.   The lowest floor (including basement) shall be at or above the flood protection elevation;
         b.   The fill shall be placed in layers no greater than six inches (6") before compaction and should extend at least ten feet (10') beyond the foundation before sloping below the flood protection elevation;
         c.   The fill shall be protected against erosion and scour during flooding by vegetative cover, riprap, or other structural measure;
         d.   The fill shall be composed of rock or soil and not incorporate debris or refuse materials; and
         e.   The fill shall not adversely affect the flow of surface drainage from or onto neighboring properties and when necessary, storm water management techniques such as swales or basins shall be incorporated; or
      2.   The building may be elevated in accordance with the following:
         a.   The building or improvements shall be elevated on stilts, piles, walls, or other foundation that is permanently open to floodwaters;
         b.   The lowest floor and all electrical, heating, ventilating, plumbing, and air conditioning equipment and utility meters shall be located at or above the flood protection elevation;
         c.   If walls are used, all enclosed areas below the flood protection elevation shall address hydrostatic pressures by allowing the automatic entry and exit of floodwaters. Designs must either be certified by a registered professional engineer or by having a minimum of one permanent opening on each wall no more than one foot (1') above grade. The openings shall provide a total net area of not less than one square inch for every one square foot of enclosed area subject to flooding below the base flood elevation;
         d.   The foundation and supporting members shall be anchored, designed, and certified so as to minimize exposure to hydrodynamic forces such as current, waves, ice and floating debris;
         e.   The finished interior grade shall not be less than the finished exterior grade;
         f.   All structural components below the flood protection elevation shall be constructed of materials resistant to flood damage;
         g.   Water and sewer pipes, electrical and telephone lines, submersible pumps, and other service facilities may be located below the flood protection elevation provided they are waterproofed; and
         h.   The area below the flood protection elevation shall be used solely for parking or building access and not later modified or occupied as habitable space.
   C.   Manufactured homes or travel trailers to be permanently installed on site shall be:
      1.   Elevated to or above the flood protection elevation; and
      2.   Anchored to resist flotation, collapse, or lateral movement by being tied down in accordance with the rules and regulations for the Illinois mobile home tie down act issued pursuant to 77 Illinois administrative code 870.
   D.   Travel trailers and recreational vehicles on site for more than one hundred eighty (180) days shall meet the elevation requirements of subsection C of this section unless the following conditions are met:
      1.   The vehicle must be either self-propelled or towable by a light duty truck. The hitch must remain on the vehicle at all times;
      2.   The vehicle must not be attached to external structures such as decks and porches;
      3.   The vehicle must be designed solely for recreation, camping, travel, or seasonal use rather than as a permanent dwelling;
      4.   The vehicle's largest horizontal projections must be no larger than four hundred (400) square feet;
      5.   The vehicle's wheels must remain on axles and inflated;
      6.   Air conditioning units must be attached to the frame so as to be safe for movement out of the floodplain;
      7.   Propane tanks, electrical and sewage connections must be quick disconnect and above the 100-year flood elevation;
      8.   The vehicle must be licensed and titled as a recreational vehicle or park model;
      9.   The vehicle must be either: a) entirely supported by jacks rather than blocks or b) have a hitch jack permanently mounted, have the tires touching the ground, and be supported by blocks in a manner that will allow the blocks to be easily removed by use of the hitch jack.
   E.   Nonresidential buildings may be structurally dry floodproofed (in lieu of elevation) provided a registered professional engineer or architect certifies that:
      1.   Below the flood protection elevation the structure and attendant utility facilities are watertight and capable of resisting the effects of the base flood;
      2.   The building design accounts for flood velocities, duration, rate of rise, hydrostatic and hydrodynamic forces, the effects of buoyancy, and the impact from debris and ice; and
      3.   Floodproofing measures will be incorporated into the building design and operable without human intervention and without an outside source of electricity. Levees, berms, floodwalls and similar works are not considered floodproofing for the purpose of this subsection.
   F.   Garages or sheds constructed ancillary to a residential use may be permitted provided the following conditions are met:
      1.   The garage or shed must be nonhabitable;
      2.   The garage or shed must be used only for the storage of vehicles and tools and cannot be modified later into another use;
      3.   The garage or shed must be located outside of the floodway;
      4.   The garage or shed must be on a single-family lot and be accessory to an existing principal structure on the same lot;
      5.   Below the base flood elevation, the garage or shed must be built of materials not susceptible to flood damage;
      6.   All utilities, plumbing, heating, air conditioning and electrical must be elevated above the flood protection elevation;
      7.   The garage or shed must have at least one permanent opening on each wall no more than one foot (1') above grade with one square inch of opening for every square foot of floor area;
      8.   The garage or shed must be less than seven thousand five hundred dollars ($7,500.00) in market value or replacement cost, whichever is greater, or less than five hundred (500) square feet;
      9.   The structure shall be anchored to resist flotation and overturning;
      10.   All flammable or toxic materials (gasoline, paint, insecticides, fertilizers, etc.) shall be stored above the flood protection elevation;
      11.   The lowest floor elevation should be documented and the owner advised of the flood insurance implications.
   G.   A building may be constructed with a crawl space located below the flood protection elevation provided that the following conditions are met:
      1.   The building must be designed and adequately anchored to resist flotation, collapse, and lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy;
      2.   Any enclosed area below the flood protection elevation shall have openings that equalize hydrostatic pressures by allowing for the automatic entry and exit of floodwaters. A minimum of one opening on each wall having a total net area of not less than one square inch per one square foot of enclosed area. The openings shall be no more than one foot (1') above grade;
      3.   The interior grade of the crawl space below the flood protection elevation must not be more than two feet (2') below the lowest adjacent exterior grade;
      4.   The interior height of the crawl space measured from the interior grade of the crawl to the top of the foundation wall must not exceed four feet (4') at any point;
      5.   An adequate drainage system must be installed to remove floodwaters from the interior area of the crawl space within a reasonable period of time after a flood event;
      6.   Portions of the building below the flood protection elevation must be constructed with materials resistant to flood damage;
      7.   Utility systems within the crawl space must be elevated above the flood protection elevation. (Ord. 04-02, 4-12-2004)