Fire hydrant locations and standards shall include:
(A) Fire hydrants shall be installed a maximum of 1,000 feet apart, or no further than 500 feet from any lot within the subdivision. Measurements along street center lines will be made to determine compliance with this requirement;
(B) Fire hydrant construction standards shall comply with the public water supplier standards serving the subdivision site;
(C) Fire hydrants shall flow a minimum 500 gallons per minute with a residual of 20 psi (pounds per square inch); and
(D) Fire hydrants are not required for subdivisions that qualify as an exempt subdivision.
(Ord. passed 4-17-1989; Ord. 11, passed 12-6-1999; Ord. 12, passed 3-19-2001; Ord. passed 1-20-2004; Ord. 17, passed 11-21-2005; Ord. 25, passed 2-16-2009)